Skip to main content

WirelessHART Gateway

MODBUS WirelessHART Gateway WHA-GW-F2D2-0-A*-Z2-ETH

wireless hart gateway

Used for data aquisition of new and historic HART instruments, enabling stranded smart instruments to provide greater monitoring capability.

The gateway is a low cost option to replacing and rewiring existing instrumentation and plant. When used with wireless HART adapters the network will create a self healing HART wireless mesh.

High cost savings compared with instrument replacements, and provides the HART 1-4 variables for plant condition alarms, maintanence alarms and forward planning.

Model

MODBUS WirelessHART Gateway WHA-GW-F2D2-0-A*-Z2-ETH>

  • Graphical network analysis
  • Simple and automatic configuration options
  • Ethernet and RS 485 interface
  • HART and MODBUS protocol via both interfaces
  • Input WirelessHART wireless interface
  • 24 V DC supply
  • Redundant power supply connections

Technical data of WHA-GW-F2D2-0-A*-Z2-ETH

Supply

  • Rated voltage 20 ... 30 V DC SELV/PELV
  • Power consumption < 5 W

External bus

  • Connection screw terminals for :- 0.2 ... 4 mm2 (rigid wire), - 0.2 ... 2.5 mm2 (flexible wire)
  • Interface 1 Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation
  • Protocol HART UDP, MODBUS TCP
  • Interface 2 RS-485
  • Protocol HART, MODBUS RTU
  • Transfer rate max. 115 kBit/s

Electrical isolation

  • Interface/interface basic insulation according to IEC 61140, rated insulation voltage 50 Veff

Directive conformity

  • Electromagnetic compatibility
  • Directive 2004/108/EC EN 61326-1:2006
  • Radio and telecommunication terminal equipment The usage of 2.4 GHz equipment is bound to local  restrictions. Ensure that restrictions allow usage of this product before commisioning.
  • Directive 99/5/EC EN 300328: V1.7.1, EN 301489-17: V1.3.2
  • FCC CFR47 Part 15 B and C ANSI C63.4-2003

Conformity

  • Degree of protection IEC 60529

Ambient conditions

  • Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
  • Storage temperature -40 ... 85 °C (-40 ... 185 °F)
  • Corrosion resistance acc. to ISA-S71.04-1985, severity level G3, test setup and execution acc. to EN 60068-2-60

Mechanical specifications

  • Degree of protection IP66/IP67
  • Mass approx. 1 kg
  • Dimensions 258 mm x 114 mm x 84 mm, without antenna and cable glands
  • Mounting panel mounting

Data for application in connection with Ex-areas

  • EC-Type Examination Certificate FM 12 ATEX 0061 , for additional certificates see www.pepperl-fuchs.com
  • Group, category, type of protection, temperature class Ex-Hexagon II 3 G Ex nA nC IIC T4 Gc
  • Directive conformity
  • Directive 94/9/EC EN 60079-0:2012
  • EN 60079-15:2010

 

Download Datasheet (Not Available) Download Manual (Not Available)

If you require further information on this product or would like a quotation, please contact dp-flow on:

Supplied by DP-Flow